General
Information
| Water
and Water Based Liquids/Oil
and Oil-Based Liquids |
| CD765
Process Monitor |
| |
Features
- 4-20 mA, ± 10 V, TC & RTD Inputs
- NEMA 4X, IP65 Front
- Shallow Depth Case 3.6" Behind Panel
- Universal Power Supply 85-265 VAC
- Two Relays Option with Alternation & Time Delays
- 4-20 mA Analog Output Option
- 24 VDC @ 200 mA Transmitter Power Option
- RS-232, RS-422/485 Serial Communication Options
- Modbus® RTU Option & Free LabVIEW™ Driver
- Sunlight Readable Display
- 3 Year Warranty
|
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
-
Display: 0.56" (14.2
mm) red LED, 4 digits (-1999 to 9999)
-
Display Intensity: Eight
user selectable intensity levels
-
Front Panel: NEMA 4X, IP65;
panel gasket provided
-
Programming Methods: Four
front panel buttons, cloning with Copy feature, PC with MeterView
or LabVIEW software, and Modbus registers. Certified LabVIEW
driver available.
-
Noise Filter: Programmable
2 to 199 (0 will disable filter)
-
Display Update Rate: Process/RTD:
3.7-5/sec; TC: 1.8-2.5/sec
-
Overrange: Display flashes
9999
-
Underrange: Display flashes
-1999
-
Recalibration: All inputs
are calibrated at the factory; recalibration is recommended
at least every 12 months.
-
Max/Min Display: Stored
until reset by user or meter is turned off.
-
Password: Restricts modification
of programmed settings.
-
Non-Volatile Memory: Settings
stored for a minimum of 10 years.
-
Power Options: 85-265 VAC,
50/60 Hz; 90-265 VDC, 20 W max or 12-36 VDC; 12-24 VAC, 6 W
max.
-
Required Fuse: UL Recognized,
5 A max, slow-blow; up to 6 meters may share one fuse.
-
Normal Mode Rejection:
64 dB at 50/60 Hz
-
Isolation: 4 kV input/output-to-power
line; 500 V input-to-output or output-to-24 VDC supplies
-
Operating Temperature:
0 to 65°C
-
Storage Temperature: -40
to 85°C
-
Relative Humidity: 0 to
90% non-condensing
-
Connections: Power &
Signal: removable screw terminal blocks accept 12 to 22 AWG.
Serial: RJ11 header, standard on all meters.
-
Enclosure: 1/8 DIN, high
impact plastic, 94V-0, color; gray
-
Weight: 9.5 oz (269 g)
(including options)
-
UL File Number: E160849;
508 Industrial Control Equipment
-
Warranty: 3 years parts
& labor
-
Extended Warranty: 1 or
2 years, refer to Price List for details.
-
Inputs: Field selectable:
0-20 mA, 4-20 mA, 1-5 V, ±10 V
-
Accuracy: ±0.05%
FS ±1 count; square root: ±0.1% FS ±2 counts
-
Function: Linear or square
root
-
Low-Flow Cutoff: 0 to 9999
(0 disables cutoff function)
-
Decimal Point: Up to 3
decimals: d.ddd, dd.dd, ddd.d, or dddd
-
Calibration: Scale without
signal or calibrate with signal source
-
Calibration Range: User
programmable over entire range of meter
-
Input Impedance: Voltage
range: greater than 1 M?,
-
Current range: 50-100 ?,
varies with resettable fuse impedance
-
Input Overload: Protected
by automatically resettable fuse
-
Temperature Drift: ±50
PPM/°C
-
Transmitter Supply: Isolated,
one or two transmitter supplies
P1: 24 VDC ±10% @ 200 mA max (-1 option)
P1 & P2: 24 VDC ±10% @ 200 mA & 40 mA max (-2
option)
-
Inputs: Factory calibrated,
field selectable: type J, K, T, or E thermocouples and 100 ?
platinum RTD (0.00385 or 0.00392 curve)
-
Resolution: 1°; type
T: 1° or 0.1°
-
Cold Junction Reference: Automatic
-
Temperature Drift: ±2°C
maximum
-
Offset Adjustment: Programmable
to ±19.9°. This parameter allows the user to apply
an offset value to the temperature being displayed.
-
Input Impedance: Greater
than 100 k?
-
Sensor Break: All relays
and alarm status LEDs go to alarm state.
|
|
| Download |
 |
CD765
Process Monitor
Datasheet
|
|
|
|